The Technical Features
1.Name and classification
(1)Name:HZDL-200A Primary Current Injection Tester
(2)Environmental groups: belong to GB6587.1-86 in "electronic measuring instrument test master plan" Ⅲ group instrument (can be used in outdoor environment).
2. 1 Input voltage: AC240V ±10%
2. 2 Power:1kVA
2. 3 Output:AC 0~200A 5V
2. 4 Output waveform: the output current is the standard sinusoidal wave with small burrs, which is better than the standard power system requirements.
2. 5 Measuring accuracy :(using grade 0.2S material) the actual value is around 0.3; Each current can be smoothly, smoothly and continuously adjustable, and the precision is higher than 0.5 level. The current voltmeter shows true and effective value with high accuracy and stability.
2.6 Output current mode: true RMS value is continuously adjustable;
2.7 current stability: 0.2%
2.8 structure and form: integrated
2.9 wiring mode: according to requirements
2.10 protection Settings: over-current and over-voltage
2.11 0.001S-99999.999S