Ranges and Accuracy of Measurement
Mode | Range | Resolution | Accuracy |
Resistance | 0.010Ω-0.099Ω | 0.001Ω | ±(1%+0.01Ω) |
0.10Ω-0.99Ω | 0.01Ω | ±(1%+0.01Ω) | |
1.0Ω-49.9Ω | 0.1Ω | ±(1%+0.1Ω) | |
50.0Ω-99.5Ω | 0.5Ω | ±(1.5%+0.5Ω) | |
100Ω-199Ω | 1Ω | ±(2%+1Ω) | |
200Ω-395Ω | 5Ω | ±(5%+5Ω) | |
400-590Ω | 10Ω | ±(10%+10Ω) | |
600Ω-880Ω | 20Ω | ±(20%+20Ω) | |
900Ω-1200Ω | 30Ω | ±(25%+30Ω) | |
*Current (True-RMS) | 0.00mA -9.00mA | 0.05mA | ±(2.5%+2mA) |
10.0mA -99.0mA | 0.1mA | ±(2.5%+10mA) | |
100mA -300mA | 1mA | ±(2.5%+20mA) | |
0.30A-2.99A | 0.01A | ±(2.5%+0.1A) | |
3.0A-9.9A | 0.1A | ±(2.5%+0.5A) | |
10.0A-20.0A | 0.1 A | ±(2.5%+1 A) |
Resistance Measurement Frequency: >1KHz
Measured Current Frequency: 50Hz/60Hz
Setting Range of Resistance Alarm Critical Value: 1Ω-199Ω
*Setting Range of Current Alarm Critical Value:1mA -499mA
Instrument safety: IEC/EN61010-1, IEC/EN6010-2-032
Insulation: double insulation
Pollution degree: class II
Overvoltage category: CAT III 150V to ground, Max 20A
Degrees of protection:
-IP30, Group III equipment as per EN 60529 Ed 92
-IK04, as per EN 50102 Ed 95
Dimensions(L×W×H):
-Long elliptic jaw: 285mm×90mm×66mm; (11×4×3 inches)
-Round jaw: 260mm×90mm×66mm;(10×4×3 inches)
Span of Jaw: Long elliptic jaw 35mm; round jaw 32mm
Weight (including batteries): Long elliptic jaw-1160g, Round jaw-1120g
Battery type: 4 ×1.5V alkaline LR6 AA battery
Low battery indication: is displayed
Internal consumption: <50mA
Auto Power off: after 5 minutes of idleness
Display: 4 LCD, sign, decimal point and backlight
Memory size: 99 Units of Reading
Environment (Temperature & Relative Humidity):
-Working: -10°C~55°C, 10%RH-90%RH
-Storage: -20°C ~60°C, below 70%RH
Range shift: Full range automatic shifting
External magnetic field: <40A/m
External electric field: <1V/m
Data upload interface: RS232 (Optional)