Detect main insulation faults of power cables of voltage class 35kV and below; calibrate cable length; accurately detect cable burial direction and depth.
II. Configuration
Cable fault location system | Name | Model | QTY |
TDR | HZ-501B | 1 | |
Pinpionter Cable route tracer | HZ-503 HZ-504 | 1 | |
High voltage generator | HZ-535-4 | 1 |
III.Main Technical data
1) Low-voltage pulse, high-voltage flashover method, audio method, acousto-magnetic synchronization method, electromagnetic induction method, DC impact
2) Test range: test distance: 60km, detection depth: 2-5m;
3) Impact high voltage: 0~35KV optional
4) Short circuit current: 0 ~ 320mA
5) Burn through power: 0 ~ 2450J
High voltage generator HZ-535-4
1) the main performance characteristics:
★With over-current, over-voltage, over-heat automatic protection function;
★ Uniform and controllable high-voltage pulse output;
★ Super short-circuit protection function, which can make the high-voltage output directly short-circuit to the ground;
★ It has dual 1.5-level pointer meter display for current and voltage, which is intuitive and clear, and the impact discharge process is clear at a glance;
★ High-voltage side voltage measurement, real-time and accurate;
★ With zero start protection, and potentiometer zero output function, safe and reliable;
★ Unique high-voltage measurement design, in the stopped state, the voltmeter can indicate the capacitor voltage in real time;
★ It has an emergency stop function, which can cut off the high voltage output in an emergency;
Main technical indicators:
Impact high voltage: 0~35kV optional
High voltage divider: voltage accuracy level 1.5
Built-in capacitance: 4μF
Discharge power: 0-2450J Charge current: 320mA
Output voltage polarity: negative polarity
Impact power: 400W
Overcurrent protection: 16A (more than 3 seconds)
Over temperature protection: 85°C
Volume: 430L×345W×545H
Weight: not more than 40kg
Working power supply: AC 220V±10%/50Hz±2Hz
Ambient temperature: -20~+60℃